Nedan hittar du felkoderna för Broan B180H75RT.
E01 Supply damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the
E10 Recirculation damper timeout damper system). Plug the unit.
E11 Recirculation damper compartment, check if connector J6 (blue) is well inserted, check for any loose
E02 Supply damper timeout damper system). Plug the unit.
E22 Supply airflow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean filters, distribution registers and outside supply hood. Inspect
E23 Supply motor (drive over current) STEP 1: Unplug/plug the unit. If STEP 1 did not fix the problem, perform STEP 2: Remove core and clear the
E24 Supply motor (drive over voltage) STEP 1: Unplug/plug the unit. Under and over voltage may be detected with severe in-house power supply fluctuation and stop the motor for protection.
E25 Supply motor (drive under voltage) If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
E26 Supply motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)
E27 Supply motor (drive foc duration) ventilation wheel from any dirt or obstacles.
E28 Supply motor (drive speed feedback) connect a spare blower system. If it works, replace supply blower.
E29 Supply motor (startup) E24 Supply motor (drive over voltage) STEP 1: Unplug/plug the unit. Under and over voltage may be detected with
E03 Supply damper If STEP 1 did not fix the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any loose
E32 Exhaust airflow STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean filters, distribution registers and outside exhaust hood. Make sure
E33 Exhaust motor (drive over current) STEP 1: Unplug/plug the unit. If STEP 1 did not fix the problem, perform STEP 2: Remove core and clear the
E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug the unit. Under and over voltage may be detected with severe in-house power supply fluctuation and stop the motor for protection.
E35 Exhaust motor (drive under voltage) If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
E36 Exhaust motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)
E37 Exhaust motor (drive foc duration) ventilation wheel from any dirt or obstacles.
E38 Exhaust motor (drive speed connect a spare blower system. If it works, replace exhaust blower.
E39 Exhaust motor (startup) E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug the unit. Under and over voltage may be detected with
E40 Outside air thermistor STEP 1: Check if thermistor is well connected in connector J7A. If STEP 1 did not fix the problem, perform STEP 2: Disconnect connector J7A and
E41 Distribution air thermistor STEP 1: Check if thermistor is well connected in connector J7B. If STEP 1 did not fix the problem, perform STEP 2: Disconnect connector J7B and
E42 PCBA thermistor fault STEP 1: Replace the electronic assembly. E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within
E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)
E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the
E50 Wall control communication lost STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not fix the problem, perform STEP 2: Remove wall control from the
E51 Wall control sensor STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not fix the problem, perform STEP 2: Replace the wall control.
E06 Exhaust damper timeout damper system). Plug the unit.
E60 Protection mode STEP 1: Perform general inspection of the unit (dampers, core, filters). 22
E07 Exhaust damper compartment, check if connector J7 (red) is well inserted, check for any loose
E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the
Hjälp
Har du frågor om luftkonditionering B180H75RT från Broan? Ställ dem direkt till vår expert! Du får information, praktiska tips och skräddarsydda lösningar på bara några sekunder.
Relaterade bruksanvisningar
Nedan hittar du bruksanvisningar för luftkonditionering som liknar B180H75RT. Prova även att se alla Broan luftkonditionering bruksanvisningar
Diskussion
Lämna en kommentar eller ställ en fråga
Delta i diskussionen
Ställ en fråga om bruksanvisningen eller lägg till ett användbart svar för andra användare.