Nedan hittar du felkoderna för Broan V160H75RS.

E01

E01 Supply damper range STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the

E10

E10 Recirculation damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical

E11

E11 Recirculation damper compartment, check if connector J6 (blue) is well inserted, check for any

E02

E02 Supply damper timeout damper system). Plug unit.

E22

E22 Supply airow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean lters, distribution registers and outside supply hood. Inspect

E23

E23 Supply motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear

E24

E24 Supply motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection.

E25

E25 Supply motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly.

E26

E26 Supply motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)

E27

E27 Supply motor (drive foc duration) the ventilation wheel from any dirt or obstacles. If STEP 2 did not x the problem, perform STEP 3: Disconnect J2 (white) and

E28

E28 Supply motor (drive speed feedback) connect a spare blower system. If it works, replace supply blower.

E29

E29 Supply motor (startup) assembly.

E03

E03 Supply damper If STEP 1 did not x the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any

E32

E32 Exhaust airow STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean lters, distribution registers and outside exhaust hood. Make

E33

E33 Exhaust motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove core and clear the

E34

E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply uctuation and stop the motor for protection.

E35

E35 Exhaust motor (drive under voltage) If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly.

E36

E36 Exhaust motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)

E37

E37 Exhaust motor (drive foc duration) ventilation wheel from any dirt or obstacles.

E38

E38 Exhaust motor (drive speed connect a spare blower system. If it works, replace exhaust blower.

E39

E39 Exhaust motor (startup) assembly. E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with

E40

E40 Outside air thermistor STEP 1: Check if thermistor is well connected in connector J7A. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7A

E41

E41 Distribution air thermistor STEP 1: Check if thermistor is well connected in connector J7B. If STEP 1 did not x the problem, perform STEP 2: Disconnect connector J7B

E42

E42 PCBA thermistor fault STEP 1: Replace the electronic assembly. E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures

E43

E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)

E05

E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the

E50

E50 Wall control communication lost STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Remove wall control from

E51

E51 Wall control sensor STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not x the problem, perform STEP 2: Replace the wall control.

E06

E06 Exhaust damper timeout damper system). Plug the unit. If STEP 1 did not x the problem, perform STEP 2: Open electrical

E60

E60 Protection mode STEP 1: Perform general inspection of the unit (dampers, core, lters). 21

E07

E07 Exhaust damper compartment, check if connector J7 (red) is well inserted, check for any

E09

E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (lters and core may have to be removed to access the

Hjälp

Har du frågor om luftkonditionering V160H75RS från Broan? Ställ dem direkt till vår expert! Du får information, praktiska tips och skräddarsydda lösningar på bara några sekunder.

Nedan hittar du bruksanvisningar för luftkonditionering som liknar V160H75RS. Prova även att se alla Broan luftkonditionering bruksanvisningar

Diskussion

Lämna en kommentar eller ställ en fråga

Delta i diskussionen

Ställ en fråga om bruksanvisningen eller lägg till ett användbart svar för andra användare.

Ange ditt meddelande här
Ange ditt namn
Ange din e-postadress